Type: | Insulated |
---|---|
Conductor Type: | Stranded |
Application: | Overhead, Heating, Underground |
Conductor Material: | Copper/Aluminum/CCA |
Sheath Material: | PVC |
Insulation Material: | PVC |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
1.Application
The product is manufactured according to the stand of GB12706 or IEC,BS,upon request, which is suitable for power installation fixed wiring or flexible connection for electrical appliances with rated voltage up to and including 450/750V respectively
2.Standard:
IEC60227,BS6004,GB/T 5023,JB/T 8734
Use characteristics: The long-term allowable working temperature of the cable core should not exceed 70ºC, and the laying temperature of the cable should not be lower than 0ºC.
Allowable bending radius: when the cable outer diameter (D) is less than 25mm, the allowable bending radius of the cable should be not less than 4D; when the cable outer diameter (D) is 25mm and above, the allowable bending radius of the cable should be not less than 6D.
Nominal section mm² |
No. of Strands No./Dia.(mm) |
Insulation Thickness mm |
Overall Jacket Thickness mm |
Approx. Wt. kg/km |
Minimum insulation resistance at 70°C Ω·km |
H05V-K | |||||
0.5 | 16/0.2 | 0.6 | 2.6 | 9.1 | 12 |
0.75 | 24/0.2 | 0.6 | 2.8 | 12.2 | 10 |
1.0 | 32/0.2 | 0.6 | 3.0 | 15.1 | 10 |
H07V-K | |||||
1.5 | 30/0.25 | 0.7 | 3.5 | 21.4 | 10 |
2.5 | 49/0.25 | 0.8 | 4.2 | 24.5 | 9.0 |
4 | 56/0.30 | 0.8 | 4.8 | 51.8 | 7.0 |
6 | 84/0.30 | 0.8 | 6.4 | 74.1 | 6.7 |
10 | 80/0.40 | 1.0 | 8.0 | 120 | 5.6 |
16 | 126/0.40 | 1.0 | 8.8 | 211 | 4.6 |
25 | 196/0.40 | 1.2 | 11.0 | 303 | 4.4 |
35 | 276/0.40 | 1.2 | 12.5 | 417 | 3.8 |